Problem
Preheat is depressed:
no preheat.
Preheat is depressed:
fuel pump does not
operate.
Preheat is depressed:
no
fuel solenoid activation.
ENGINE TROUBLESHOOTING
probable Cause
1.
Connection
or
switch.
2.
Preheat solenoid.
3.
Glow plugs are
faulty.
1.
Faulty connections
or
bad pump.
1.
Faulty connections
or
solenoid.
2.
Voltage problem.
63
Verification/Remedy
1.
Check
for
12 volts at the
PREHEAT switch and at the
S terminal on the preheat
solenoid.
2.
No
activation with 12 volts
at the
S terminal. Tap solenoid
with a mallet
to
determine if it
is stuck internally. Solenoid
should produce a click when
activated and when deactivated.
3.
Twelve volts are present at
the glow plugs. Remove each
plug and check the resistance
of the plugs
by
applying
12
volts
artificially.
1.
Check
for
12 volts at the
fuel
pump
connections.
If 12 volts are present, the
pump is possibly faulty.
Tap pump with a mallet.
Pump's plunger may be stuck.
Remove the filter and check for
contamination which will affect
the pump.
1.
Check
for
12 volts at ( + )
positive terminal at the back
of the fuel solenoid when the
PREHEAT button is depressed.
Twelve volts with no activation
indicates a faulty solenoid.
2.
Less than
10
volts found at the
positive ( + ) terminal on the
solenoid will not properly
activate the solenoid and will
cause a failure. Check for low
batteries
or
voltage loss
in
small electrical wiring
or
corroded connections.
Westerbeke Generators