To STOP
lhe
the STOP which opens the closed B +
and
START
switches. The STOP switch must
be
held open until the comes
to
a
""'''nl,,'''
Remote start panels may be connected
to
the set as indicated. A has
to
be removed be·
tween the
T·j
and T-2 connections at the connection terminal board. (ReIer
to
the diagram in
the «ELECTRICAL
SYSTEM«
section of this page 46, lower left·hend corneL)
When installing
the
optional remote slart panel
or
Ihe optional remote instrument
responsibility
to
comply with
U.S.
Coast Guard Standards 33
CFR
PART
183.
Cormecling
Pressure Sensing Devices
to
Oil
Galleries
~
is
the installer's
Oil
pressure sensing devices, such as senders and switches, must never be connected directly to any oil
gallery
of
an engine. The reason
is
simply that continued engine vibration causes fatigue
of
the fittings used
to
make such a connection. If these fittings fail, the engine loses its oil pressure and quickly seizes.
Such pressure sensing devices must be bulkhead·mounted and connected to the oil gallery using an ap·
propriate grade of lubricating oil hose. Any fittings used
to
connect the hose
to
the gallery must be
of
steel
or
malleable iron composition. Brass must not be used for this application.