SAFETY
SHUTDOWN
SENSORS
AND
SWITCHES
SAFm
SHUTDOWN
SWITCH/SENSORS
The engine is protected
by
four automatic
shutdown
circuits.
Should a shutdown
occur,
do not attempt to resflJtt without
finding
and
correcting the cause. Refer to the
heading
Engine statts, runs
and
then shuts down
in
the
ENGINE
TROUBLESHOOTING section of this
manual.
The following
is
a description of
these
automatic
shutdown
circuits:
lil.-.
Exhaust
Temperature
Switch
An exhaust temperature switch
is
located
on
the
water
injected exhaust
elbow.
Normally closed, this
switch
will
open
and the ECU will interpret this
as
a
high
exhaust
temperature and open
the
K2
run
relay,
stopping
the
generator. The exhaust temperature
LED
on
the
panel
will
illuminate. The switch
opens
at
26(}.270F
(I27-132C).
This
switch resets (contacts close)
at
approximately 225F (I07C).
HIGH
EXHAUST
.
nMPERATURE
SWITCH
water
Temperature
Sensor
If
fi
MOUNTED
ATTHE
EXHAUST
ELBOW
A water temperature sensor
is
located at
the
thermostat
housing. This sensor
sends
a
DC
voltage to
the
ECU
that
it
interprets
as
engine antifreeze coolant temperature.
Should
this
voltage reach a set
value,
the
ECU
will
interpret
this
as
high antifreeze coolant temperature and
open
the
K2
run
relay,
stopping
the
generator.
The overheat
LED
on
the
panel
will
then illuminate.
Oil
Pressure
Sensor
An
oil
pressure sensor
is
located off
the
engines
oil
gallery.
Oil
pressure
on
the
sensor
affects
the
DC
voltage
through
the
sensor to
the
ECU.
Should
the
voltage
reach
a preset
value,
the
ECU
will
interpret
this
as
a
low
oil
pressure
issue
and
open
the
K2
run
relay,
stopping
the
generator.
The
oil
pressure
LED
on
the
panel
will
illuminate.
Engine
DC
Circuit
Breaker
OIL
PRESSURE
SENSOR
The generator's engine DC circuit
is
protected
by
a rocker
type
DC
20
amp
breaker
mounted
on
the
control
box.
This
also serves as an Emergency Stop Switch. Excessive
DC
current draw
or
DC
electrical overload anywhere
in
the
instrument
paneJ
wiring
or
engine
wiring
will
cause
the
breaker to
trip
to
the
OFF
position.
In
this
event,
the
DC
power to
the
ECU
will
be
interrupted, stopping
the
generator.
No
panel
LED
will
illuminate. Check
and
repair
the
source
of
the
problem. After repairing
the
fault,
reset
the
breaker
and
restart the
generator.
Hlgh/Low
RPM
Shutdown
Should the generator's
RPM
go
above
20%
of
the specified
1800 rpm @ 60 HzJI500
rpm
@ 50 Hz, the ECU
will
shut
the engine
down
on
an
over speed fault
and
illuminate
the
over speed
LED
on
the
control
panel
and
remote start/stop
panel
when
installed
Should the generator's
RPM
fall
below
20%
of the specified
1800
rpm @ 60
HZ/15oo
rpm @ 50
Hz,
the ECU
will
shut
the
engine
down
on
an
under speed fault
and
this
will
cause
the over speed
LED
to
flash.
The
OBD
(On
Board
Diagnostic)
will
also
show
these
faults.
Engines & Generators